8030-ROM-441
Call Today!
|
||
8030-ROM-441 Information: |
8030-ROM-441. Symax Class 8030 Type ROM-441 24V VDC 32 Function Output Module. Optical isolation. Maximum surge current 3 Amp for 300 usec. Duty cycle less than or equal to 2%. 980 mA rated current draw at 100% duty cycle. Maximum output 0.5 Amps per output, 12 Amps per module. See application considerations for minimum load current. Voltage operating range 21-29 VDC.